kapı motoru pendik escort porna kadıköy escort kadıköy escort pendik escort kurtköy escort maltepe escort kadıköy Escort kurtköy escort kartal escort ümraniye escort kartal escort bahçeşehir escort pendik escort izmir escort bodrum escort mersin escort ataköy escort bayan bakırköy escort Şirinevler Escort ankara escort Avcılar escort sex izle ankara escort ankara escort Şişli Escort etiler escort beylikdüzü escort escort eskişehir ankara escort Taksim Escort kocaeli escort beşiktaş escort avcılar escort beylikdüzü escort halkalı escort istanbul escort escort ankara ankara escort Specification - BCH India-Switchgear Manufacturers|LV Panel Manufacturers

Specification

contractor-overview4.png

CONTACTOR GENERAL CHARACTERISTICS Standard – IS/IEC 60947-4-1

CONTRACTOR CAT. REFERENCE - CE15AN .3.B, CE15BN .3.B, CE15CN .3.B

CONTACTOR GENERAL CHARACTERISTICS Standard – IS/IEC 60947-4-1
Operating temperature : 20C to +60C 1
Operating altitude : 2000m
Humidity: 50% RH at 60C
95% at 40C
Vibration: 5 to 100 Hz (0.7g in x,y,z plane)
Operating position: 30
CONTACTOR CAT. REFERENCE CE15DN3-B CE15EN3-B CE15FN3-B
Nominal current rating at 380/415V 50Hz (AC3 duty) Ie (A) 18 25 32
Standard power rating at 380V / 415V 50Hz P (kW) 9.0/9.0 11/11 15/15
Electrical endurance at rated current AC3 duty Million 1.5 1.5 1.7
Maximum frequency of no load operation op/h 600 600 600
MECHANICAL DATA
Frame size mm 45
Number of poles 3 3 3
Overall dimensions (LxBxH) mm 75x45x84 75x45x84 75x45x84
Mounting dimensions mm M4 34.5×60 M4 34.5×60 M4 34.5×60
Weight Kg 0.44 0.44 0.44
Mechanical durability Million 20 20 20
POWER CIRCUIT
Operational voltage Ue (V) 660 660 660
Insulation voltage Ui (V) 690 690 690
Impulse voltage withstand kV 6 6 6
Thermal current Ith (A) 32 40 40
Connections mm2 6 6 6
AC-1 duty rated at 380/415V 50Hz (40°C) Ie (A) 32 40 40
AC-4 duty rated at 380/415V 50Hz Ie (A) 16 23 23
Electrical life at rated current AC4 duty ops. 67000 52000 75000
AC-4 duty rating for 200000 operations Ie (A) 8.3 10 12
Stator current rating acc. to AC2 duty (A) 55C 100% DF 16 25 32
Rotor duty rating-delta Connected (A) 40C 100% DF 29 40 52
60% DF 38 51 67
40% DF 47 63 82
20% DF 66 89 116
Maximum rotor voltage – starting & inching
Starting & plugging
Transformer primary switching 500V AC A 7.6 10 13
Capacitor switching(single bank only) 380/400V, 3ph kVAR 12 15 15
CONTROL CIRCUIT
Coil VA consumption Pickup VA 92
Seal VA 8

CONTRACTOR CAT. REFERENCE - CE15DN .3.B, CE15EN .3.B, CE15FN .3.B

CONTACTOR GENERAL CHARACTERISTICS Standard – IS/IEC 60947-4-1
Operating temperature : 20C to +60C 2
Operating altitude : 2000m
Humidity : 50% RH at 40C
90% RH at 20C
Vibration : 5 to 100 Hz (0.7g in x,y,z plane)
Operating position : 30
CONTACTOR CAT. REFERENCE CE15AN-3-B CE15BN-3-B CE15CN-3-B
Nominal current rating at 380/415V 50Hz (AC3 duty) Ie (A) 6 9 12
Standard power rating at 380V / 415V 50Hz P (kW) 2.2/2.2 4/4 5.5/5.5
Electrical endurance at rated current AC3 duty Million 2.7 2.3 2.1
Maximum frequency of no load operation op/h 600 600 600
MECHANICAL DATA
Frame size mm 45
Number of poles 4 4 4
Overall dimensions (LxBxH) mm 75x45x84 75x45x84 75x45x84
Mounting dimensions mm M4 34.5×60 M4 34.5×60 M4 34.5×60
Weight Kg 0.41 0.41 0.41
Mechanical durability Million 20 20 20
POWER CIRCUIT
Operational voltage Ue (V) 660 660 660
Insulation voltage Ui (V) 690 690 690
Impulse Voltage withstand kV 6 6 6
Thermal current Ith (A) 20 20 20
Connections mm2 2.5 2.5 2.5
AC-1 duty rated at 380/415V 50Hz (40C) Ie (A) 20 20 20
AC-4 duty rated at 380/415V 50Hz Ie (A) 6 9.1 12
Electrical life at rated current AC4 duty ops. 60000 59000 43000
AC-4 duty rating for 200000 operations Ie (A) 2.5 4.3 4.8
Stator current rating acc. to AC2 duty (A) 55C 100% DF 6 9.1 12
Rotor duty rating-Delta Connected (A) 40C 100% DF 12 16 21
60% DF 15 21 27
40% DF 19 26 33
20% DF 27 36 46
Maximum Rotor Voltage – Starting & Inching
Starting & Plugging
Transformer primary switching 500V AC A 3.1 4.2 5.4
Capacitor switching(single bank only) 380/400V, 3ph kVAR 4.9 6.7 8.6
CONTROL CIRCUIT
Coil VA Consumption Pickup VA 70
Seal VA 6.4

CONTRACTOR CAT. REFERENCE - CE15GN .3.B, CE15HN .3.B, CE15JN .3.B, CE15KN .3.B

CONTACTOR GENERAL CHARACTERISTICS Standard – IS/IEC 60947-4-1
Operating temperature : 20C to +60C 3
Operating altitude : 2000m
Humidity : 50% RH at 60C
95% RH at 40C
Vibration : 5 to 100 Hz (0.7g in x,y,z plane)
Operating position : 30
CONTACTOR CAT. REFERENCE CE15GN3  B CE15HN3  B CE15JN3  B CE15KN3  B
Nominal current rating at 380/415V 50Hz (AC3 duty) Ie (A) 40 50 65 75
Standard power rating at 380V / 415V 50Hz P (kW) 18.5/22 22/25 30/37 37/37
Electrical endurance at rated current AC3 duty Million 1.1 1.3 1.4 1.3
Maximum frequency of no load operation op/h 600 600 600 600
MECHANICAL DATA
Frame size mm 65
Number of poles 3 3 3 3
Overall dimensions (LxBxH) mm 108x65x108 108x65x108 108x65x108 108x65x108
Mounting dimensions mm M5 55×95 M5 55×95 M5 55×95 M5 55×95
Weight Kg 1.28 1.28 1.28 1.28
Mechanical durability Million 10 10 10 10
POWER CIRCUIT
Operational voltage Ue (V) 660 660 660 660
Insulation voltage Ui (V) 690 690 690 690
Impulse voltage withstand kV 6 6 6 6
Thermal current Ith (A) 60 75 80 80
Connections mm2 25 25 25 25
AC-1 duty rated at 380/415V 50Hz (40C) Ie (A) 60 75 80 80
AC-4 duty rated at 380/415V 50Hz Ie (A) 37 44 50 59
Electrical life at rated current AC4 duty ops. 58000 62000 35000 34000
AC-4 duty rating for 200000 operations Ie (A) 17 34 34 34
Stator current rating acc. to AC2 duty (A) 55C 100% DF 40 50 65 73
Rotor duty rating-Delta Connected (A) 40C 100% DF 64 76 104 126
60% DF 83 98 134 163
40% DF 101 120 164 200
20% DF 143 170 232 283
Maximum rotor voltage – starting & inching
Starting & plugging
Transformer primary switching 500V AC A 15 20 20 24
Capacitor switching(single bank only) 380/400V, 3ph kVAR 25 30 37 40
CONTROL CIRCUIT
Coil VA consumption Pickup VA 230
Seal VA 28

CONTRACTOR CAT. REFERENCE - BCH15KT .3.11.#, BCH15LT .3.11.#

CONTACTOR GENERAL CHARACTERISTICS Standard – IS/IEC 60947-4-1
Operating temperature : 20C to +60C 4 5
Operating altitude : 2000m
Humidity : 50% RH at 40C
90% RH at 20C
Vibration : 5 to 100 Hz (0.7g in x,y,z plane)
Operating position : 30
CONTACTOR CAT. REFERENCE BCH15KT.3.11. BCH15LT.3.11. BCH15MT.3.11. BCH15NT.3.11. BCH15PT.3.11.
Nominal current rating at 380/415V 50Hz (AC3 duty) Ie (A) 80 95 110 150 175
Standard power rating at 380V / 415V 50Hz P (kW) 37 / 40 45 / 47 55 / 59 75 / 80 90 / 95
Electrical endurance at rated current AC3 duty Million 0.8 0.8 0.8 0.8 0.8
Maximum frequency of no load operation op/h 3000 1200
MECHANICAL DATA
Frame size mm 79 110
Number of poles 4
Overall dimensions (LxBxH) mm 137x79x130 162x79x130 170x110x162
Mounting dimensions mm M5 70×100 M5 100×130
Weight Kg 1.8 2.2 4
Mechanical durability Million 10
POWER CIRCUIT
Operational voltage Ue (V) 1000
Insulation voltage Ui (V) 1000
Impulse voltage withstand kV 8 8 8 8 8
Thermal current Ith (A) 125 135 230 NT200 250
Connections mm2 50 120
AC-1 duty rated at 380/415V 50Hz (40C) Ie (A) 125
115kt
135 230
NT-200
250
PT
AC-4 duty rated at 380/415V 50Hz Ie (A) 80 90 110 150 175
Electrical life at rated current AC4 duty ops. 20000
AC-4 duty rating for 200000 operations Ie (A) 27 31 34 41 50
Stator current rating acc. to AC2 duty (A) 55C 100% DF 80 95 110 150 175
Rotor duty rating-delta connected (A) 40C 100% DF 160 175 224 280 350
60% DF 185 200 250 325 406
40% DF 217 236 245 380 475
20% DF 272 296 360 475 594
Maximum rotor voltage – starting & inching Delta connected -1160V ; Star connected – 1380V
Starting & plugging Delta connected – 580V ; Star connected – 690V
Transformer primary switching 500V AC A 36 40 50 65 80
Capacitor switching(single bank only) 380/400V, 3ph kVAR 40 50 60 80 100
CONTROL CIRCUIT
Coil VA consumption Pickup VA 250 350
Seal VA 19 5

CONTRACTOR CAT. REFERENCE - MCE15RN 3.7, MCE15SON 3.7, MCE15SN 3.7

CONTACTOR GENERAL CHARACTERISTICS Standard – IS/IEC 60947-4-1
Operating temperature : -20C to +60C 6
Operating altitude : 2000m
Humidity : 50% RH at 60C
95% RH at 40C
Vibration : 5 to 100 Hz (0.7g in x,y,z plane)
Operating position : 30
CONTACTOR CAT. REFERENCE MCE15RN37 MCE15S0N37 MCE15SN37
Nominal current rating at 380/415V 50Hz (AC3 duty) Ie (A) 200 265 300
Standard power rating at 380V / 415V 50Hz P (kW) 110/110 90/90 160/160
Electrical endurance at rated current AC3 duty Million 0.52 0.55 0.351
Maximum frequency of no load operation op/h 600 600 300
MECHANICAL DATA
Frame size mm 178
Number of poles 3 3 3
Overall dimensions (LxBxH) mm 250x186x195 250x186x195 250x186x195
Mounting dimensions mm M6 160×166.5 M6 160×166.5 M6 160×166.5
Weight Kg 8.3 8.3 8.3
Mechanical durability Million 5 5 5
POWER CIRCUIT
Operational voltage Ue (V) 660
Insulation voltage Ui (V) 690
Impulse voltage withstand kV 6 6 6
Thermal current Ith (A) 300 315 315
Connections mm2 240 240 240
AC-1 duty rated at 380/415V 50Hz (40C) Ie (A) 300 315 315
AC-4 duty rated at 380/415V 50Hz Ie (A) 140 165 170
Electrical life at rated current AC4 duty ops. 65000 60000 60000
AC-4 duty rating for 200000 operations Ie (A) 70 75 80
Stator current rating acc. to AC2 Duty (A) 55C 100% DF 200 265 300
Rotor duty rating-delta connected (A) 40C 100% DF 393 425 465
60% DF 507 550 600
40% DF 621 700 735
20% DF 879 950 1040
Maximum rotor voltage – starting & inching
Starting & plugging
Transformer primary switching 500V AC A 90 100 135
Capacitor switching(single bank only) 380/400V, 3ph kVAR 110 140 158
CONTROL CIRCUIT
Coil VA consumption Pickup VA 1040
Seal VA 116

CONTRACTOR CAT. REFERENCE - BCH54 .3.22.#, BCH55 .3.22.#

CONTACTOR GENERAL CHARACTERISTICS Standard – IS/IEC 60947-4-1
Operating temperature : 20C to +60C 7
Operating altitude : 2000m
Humidity : 50% RH at 60C
95% RH at 40C
Vibration : 5 to 100 Hz (0.7g in x,y,z plane)
Operating position : 30
CONTACTOR CAT. REFERENCE BCH54.3.22. BCH55.3.22. BCH57.3.22.
Nominal current rating at 380/415V 50Hz (AC3 duty) Ie (A) 400 450 550
Standard power rating at 380V / 415V 50Hz P (kW) 220/240 220/240 280×315
Electrical endurance at rated current AC3 duty Million 0.6 0.6 0.6
Maximum frequency of no load operation op/h 300 300 300
MECHANICAL DATA
Frame size mm 220
Number of poles 3 3 3
Overall dimensions (LxBxH) mm 250x220x225 250x220x225 258x220x225
Mounting dimensions mm M8 110×220 M8 110×220 M8 110×220
Weight Kg M8 110×220 13.0 13.5
Mechanical durability Million 5 5 5-10
POWER CIRCUIT
Operational voltage Ue (V) 1000 1000 1000
Insulation voltage Ui (V) 1000 1000 1000
Impulse voltage withstand kV 8 8 8
Thermal current Ith (A) 600 600 760
Connections (Cu) mm2 2(40×5) 2(40×5) 2(50×5)
AC-1 duty rated at 380/415V 50Hz (40C) Ie (A) 600 600 760
AC-4 duty rated at 380/415V 50Hz Ie (A) 400 450 550
Electrical life at rated current AC4 duty ops. 6000 6000 6000
AC-4 duty rating for 200000 operations Ie (A) 100 115 140
Stator current rating acc. to AC2 duty (A) 55C 100% DF 400 450 550
Rotor duty rating-delta connected (A) 40C 100% DF 750 840 1060
60% DF 860 960 1210
40% DF 1020 1130 1430
20% DF 1300 1420 1790
Maximum rotor voltage – starting & inching
Starting & plugging
Transformer primary switching 500V AC A 185 203 250
Capacitor switching(single bank only) 380/400V, 3ph kVAR 190 200 250
CONTROL CIRCUIT
Coil VA consumption Pickup VA 950
SealVA 11

CONTRACTOR CAT. REFERENCE - BCH57 .3.22.#, BCH62 .3.22.#

CONTACTOR GENERAL CHARACTERISTICS Standard – IS/IEC 60947-4-1
Operating temperature : 20C to +60C 8
Operating altitude : 2000m
Humidity : 50% at 60C
95% RH at 40C
Vibration : 5 to 100 Hz (0.7g in x,y,z plane)
Operating position : 30
CONTACTOR CAT. REFERENCE BCH62.3.22. BCH64.3.22.
Nominal current rating at 380/415V 50Hz (AC3 duty) Ie (A) 700 860
Standard power rating at 380V / 415V 50Hz P (kW) 375/400 475/500
Electrical endurance at rated current AC3 duty Million 0.6 0.6
Maximum frequency of no load operation op/h 300 300
MECHANICAL DATA
Frame size mm 280
Number of poles 3 3
Overall dimensions (LxBxH) mm 307x280x291 361x280x291
Mounting dimensions mm M10 175×280 M10 175×280
Weight Kg 26.4 27.6
Mechanical durability Million 5-10 5-10
POWER CIRCUIT
Operational voltage Ue (V) 1000 1000
Insulation voltage Ui (V) 1000 1000
Impulse voltage withstand kV 8 8
Thermal current Ith (A) 1000 1100
Connections (Cu) mm2 2(60×5) 2(60×6)
AC-1 duty rated at 380/415V 50Hz (40C) Ie (A) 1000 1100
AC-4 duty rated at 380/415V 50Hz Ie (A) 700 860
Electrical life at rated current AC4 duty ops. 6000 6000
AC-4 duty rating for 200000 operations Ie (A) 185 215
Stator current rating acc. to AC2 duty (A) 55C 100% DF 700 860
Rotor duty rating-delta Connected (A) 40C 100% DF 1400 1540
60% DF 1600 1760
40% DF 1890 2080
20% DF 2370 2610
Maximum Rotor Voltage – Starting & Inching
Starting & Plugging
Transformer primary switching 500V AC A 315 390
Capacitor switching(single bank only) 380/400V, 3ph kVAR 350 400
CONTROL CIRCUIT
Coil VA Consumption Pickup VA 1600
Seal VA 25

CONTRACTOR CAT. REFERENCE - BCH64 .3.22.#, BCH76 .3.22.#, BCH78 .3.22.#

CONTACTOR GENERAL CHARACTERISTICS Standard – IS/IEC 60947-4-1
Operating temperature: 20C to +60C 9
Operating altitude: 2000m
Humidity : 50% RH at 60C
95% RH at 40C
Vibration : 5 to 100 Hz (0.7g in x,y,z plane)
Operating position : 30
CONTACTOR CAT. REFERENCE BCH76.3.12. BCH78.3.12.
Nominal current rating at 380/415V 50Hz (AC3 duty) Ie (A) 1000 1200
Standard power rating at 380V / 415V 50Hz P (kW) 550/600 650/700
Electrical endurance at rated current AC3 duty Million 0.6 0.6
Maximum frequency of no load operation op/h 120 120
MECHANICAL DATA
Frame size mm 334
Number of poles 3 3
Overall dimensions (LxBxH) mm 490x334x345 490x334x345
Mounting dimensions mm M12 120×380 M12 120×380
Weight Kg 49 53
Mechanical durability Million 1-5 1-5
POWER CIRCUIT
Operational voltage Ue (V) 690 690
Insulation voltage Ui (V) 690 690
Impulse Voltage withstand kV 8 8
Thermal current Ith (A) 1200 1350
Connections (Cu) mm2 2(60×6) 2(60×6)
AC-1 duty rated at 380/415V 50Hz (40C) Ie (A) 1200 1350
AC-4 duty rated at 380/415V 50Hz Ie (A) 1000 1200
Electrical life at rated current AC4 duty ops. 6000 6000
AC-4 duty rating for 200000 operations Ie (A) 265 300
Stator current rating acc. to AC2 duty (A) 55C 100% DF 1000 1200
Rotor duty rating-delta connected (A) 40C 100% DF 1680 1850
60% DF 1930 2120
40% DF 2270 2500
20% DF 2840 3130
Maximum rotor voltage – starting & inching
Starting & Plugging
Transformer primary switching 500V AC A 450 540
Capacitor switching(single bank only) 380/400V, 3ph kVAR 450 500
CONTROL CIRCUIT
Coil VA consumption Pickup  VA 2450
Seal VA 75

BCH - Duros Freedom range of 4 Pole Contactors#


– 100% rated add-on 4th pole for flexibility (up to 80A AC1)
– Low energy consumption (seal VA up to 5 VA)

AC 1 rating(Amp) Pole Aux. contacts Cat code
Total-4P-contactor-range-info-2 20 4P CE15CN4B
32 4P CE15DN4
40 4P CE15EN4
60 4P CE15GN4
75 4P CE15HN4
80 4P CE15JN4
Total-4P-contactor-range-info-1 200 4P 1NO+1NC BCH15MN.4.11
250 4P 1NO+1NC BCH15NN.4.11
300 4P 1NO+1NC BCH15PN.4.11

 

Contactor AC coil voltage
type 24 48 110 220 415
CE15 U W A B M
BCH15 110 220 380

 

51WPrrh